—Panel Size: 48mm×48mm;48mm×96mm;72mm×72mm;96mm×96mm
—Input Signal: T: universal input; A: analog input
—Power Type: linear power supply, switch power supply
—Main Output: relay; logic level; analog output; SCR phase shift/ zero cross; 30A relay output; built-in SCR output, analog isolation
—Alarm Output: no alarm; 1 relay alarm output; 2 relay alarm output; 1 logic level alarm output and 1 relay alarm output; 1 logic level alarm output; 2 logic level alarm output; 1 relay alarm output (normally open/ normally close)
—Strengthened Function: no strengthened function; RS485 communication
—Function Code: for customized product only
—Rated Voltage: Linear power 180V-240V AC, Switch power 85V~265V AC, 50/60 HZ
—Power Consumption: ≤5VA
—Dielectric Strength: power-input: 1500V AC 1min; input-relay output: 1500V AC 1min; power-relay output: 1500V AC 1min
—Insulation Resistance: input-relay output: >20MΩ; input-power: >20MΩ; power-relay output: >20MΩ
—Working Environment: Ambient temperature: 0℃~50℃; Relative Humidity: 35%~85% (no condensation)
—Relay Output: relay contact: AC220V/ DC30V,3A (resistive load or designation)
—Logic level output: ON: DC 12V; OFF: Below DC 0.5V; Max current: 30mA; load resistance≥1K
—SCR zero cross signal: 100mA
—DC 4-20mA output: allowable load resistance below 500Ω
—Input Sensor: TC: ≤100Ω; RTD: ≤5Ω(each wire)
—Measurement Range: K(-270℃~1370℃);E(-270℃~1000℃);J(-210℃~1200℃);S(-50~1768℃);B(0℃~1820℃);N(-270℃~1300℃);R(-50℃~1768℃);T(-270℃~400℃);PT100(-200℃~850℃);Cu50(-50℃~150℃)
—Resolution: 0.1℃ (adjustable)
—Accuracy: ±0.5%FS
—This series is a multi-input product with thermocouple, Platinum resistance, analog voltage input, and analog current input
—In addition to standard controls, optional two-way PID control function (heating and cooling)
—Automatically set PID parameters (AT function)
—Communication function (Optional)
—Support user correcting sensor input
—Compliance with EMC standards